Numerical research on smoke exhaust in one shopping mall with atrium
Abstract:At present,the method of the quantity of smoke exhaust calculated by code for fire protection design of tall buildings has some problems.Combining with Jin-Ying atrium in a shopping mall,makes design of smoke exhaust in atrium using fire performance-based design method,and makes simulation of smoke control effect using FDS(Fire Dynamics Simulator).The results indicate that the quantity of smoke exhaust 443 520 m3/h calculated by the fire performance-based design method can make staff safety evacuation.
Keywords:atriumshopping mallmechanical smoke exhaustperformance-based designFDS
Publication Date:2011-01-01
Online Publishing Date:2025-08-15(First online date of this platform, not the publication date of the document)
Pages:5( 709-713 )
JOURNAL OF HENAN POLYTECHNIC UNIVERSITY

JOURNAL OF HENAN POLYTECHNIC UNIVERSITY

PKUISTIC
ISSN:1673-9787
Year, Vol.(Issue):2011,30(6)